Chiller & Process Cooling Glycol

Coolflow is Hydratech’s range of glycol and secondary-coolant fluids for chillers, process cooling, refrigeration, HVAC and air conditioning, including food and drink production. Each fluid gives frost protection and contains long-life inhibitors against corrosion, scale and biological fouling, and there are non-toxic and food-safe options for food and beverage plants.

Chillers, process cooling & HVACFood-safe options (NTP is HT1 certified)Frost protection to −50°CExceeds ASTM D1384 corrosion standards205L drums & 1000L IBCs

Compare the Coolflow range

FluidSummaryEfficiencyAntifreezeCorrosion controlToxicity% for −10°C% for −20°C
Coolflow DTXDetoxified ethylene glycol · non-toxic, food-safeABAAA22%33%Ask us
Coolflow NTPPropylene glycol · non-toxic, HT1 certifiedBCBAA25%39%Ask us
Coolflow IGEEthylene glycol · industrial · harmfulBBAAD20%*32%Ask us
Coolflow LVFPotassium formate · very low viscosityBAACBReady-mixed, −20°C to −60°CAsk us
Coolflow ECO2Refined vegetable extract · non-toxicBCBAA25%38%Ask us
Coolflow ECO3Bio-based propylene glycol · non-toxicBCBAA25%38%Ask us

Ratings are Hydratech’s own, from A (best) to E. “% for −10°C / −20°C” is the concentrate needed as a percentage of total system volume, from each fluid’s data sheet. *Hydratech’s minimum dose for Coolflow IGE is 25%.

Which Coolflow do I need?

Coolflow DTX: the all-rounder

Ethylene glycol with Hydratech’s patented DeTox™ additive, classified non-toxic and food-safe. Better heat transfer and easier pumping than propylene glycol, and less is needed for the same frost protection.

Coolflow NTP: propylene glycol

Fully inhibited propylene glycol for systems where a non-toxic classification is required, including food and beverage processing. HT1 certified.

Coolflow IGE: industrial

Inhibited ethylene glycol for industrial process cooling and air conditioning. Good thermal and pumping performance, but classed as harmful, so only where toxicity is not an issue.

Coolflow LVF: very low viscosity

Ready-to-use potassium formate, rated top for efficiency. Corrosive in contact with air, so only for closed-loop pressurised systems and certain metals. Ask us before choosing it.

Coolflow ECO2: plant-based

Based on refined vegetable extracts, renewable rather than derived from crude oil. For systems where low environmental impact is preferred.

Coolflow ECO3: bio propylene glycol

Made with bio-based propylene glycol, an alternative to petroleum-derived glycol. Slightly more efficient than ECO2, but more expensive per litre.

How much do I add?

Work out the total system volume, then add Coolflow concentrate for the lowest temperature you need to protect against. Dilute with deionised, distilled or ultrapure water, and avoid water high in calcium salts or chlorides. Hydratech recommends checking the concentration with a recently calibrated refractometer.

Frost protectionDTXNTPIGEECO2ECO3
−10°C22%25%20%25%25%
−15°C28%33%27%32%32%
−20°C33%39%32%38%38%
−25°C38%44%37%43%43%
−30°C42%48%41%48%48%
−35°C46%53%45%52%52%
Minimum dose22%25%25%25%25%

Volume of concentrate as a % of total system volume. The maximum does not normally exceed 60%. Coolflow LVF is supplied ready-to-use, so it isn’t diluted. Source: Hydratech product data sheets.

Changing or topping up a system? Use the same type of fluid that is already in it. If you’re not sure what’s in the system, contact us before adding anything.

Before filling, Hydratech advises that pipework should be clean and free of debris and biological contamination (BSRIA guide BG 29/2012), with air ingress kept to a minimum. A pressurised system is best.

Filling or changing over a chiller?

Coolflow is available in 5, 10 and 25 litre drums, 205 litre drums and 1000 litre IBCs, and every concentrate can be supplied ready-mixed to the strength you need. Tell us your system volume and operating temperature and we’ll come back with a price.

Ask for a price

No products were found matching your selection.