Biotherm is Hydratech’s range of high-temperature-rated glycol antifreeze and heat transfer fluids for domestic and commercial biomass boiler heating systems. Each fluid protects the system against freezing and has a long-life formulation with inhibitors against corrosion, scale and biological fouling.
| Fluid | Summary | Efficiency | Antifreeze | Corrosion control | Toxicity | % for −10°C | % for −20°C | |
|---|---|---|---|---|---|---|---|---|
| Biotherm DTXDetoxified ethylene glycol · non-toxic | A | B | A | A | A | 22% | 33% | Ask us |
| Biotherm BP8Propylene glycol · non-toxic | B | C | B | A | A | 25% | 39% | Ask us |
| Biotherm BE2Ethylene glycol · industrial · harmful | B | B | A | A | D | 20% | 32% | Ask us |
| Biotherm VB4Refined vegetable extract · non-toxic | B | C | B | A | A | 25% | 38% | Ask us |
Ratings are Hydratech’s own, from A (best) to E. “% for −10°C / −20°C” is the concentrate needed as a percentage of total system volume, from each fluid’s data sheet.
Ethylene glycol with Hydratech’s patented DeTox™ additive, so it is classified non-toxic. Better heat transfer and heat recovery than propylene glycol, and less is needed for the same frost protection.
The traditional non-toxic choice. Use it where propylene glycol is specified, or to top up a system that already runs on propylene glycol.
Inhibited ethylene glycol. Efficient and more cost-effective than BP8 and VB4, but classed as harmful, so only for systems where toxicity is not an issue.
Based on refined vegetable extracts, for systems where low environmental impact is preferred.
Work out the total system volume, then add Biotherm concentrate for the lowest temperature you need to protect against. Dilute with deionised, distilled or ultrapure water, and avoid water high in calcium salts or chlorides. Hydratech recommends checking the concentration with a recently calibrated refractometer.
| Frost protection | Biotherm DTX | Biotherm BP8 | Biotherm BE2 | Biotherm VB4 |
|---|---|---|---|---|
| −10°C | 22% | 25% | 20% | 25% |
| −15°C | 28% | 33% | 27% | 32% |
| −20°C | 33% | 39% | 32% | 38% |
| −25°C | 38% | 44% | 37% | 43% |
| −30°C | 42% | 48.5% | 41% | 48% |
| −35°C | 46% | 52.5% | 45% | 52% |
| Minimum dose | 22% | 25% | 20% | 25% |
Volume of concentrate as a % of total system volume. The maximum does not normally exceed 60%. Source: Hydratech product data sheets.
Topping up? Use the same type of fluid that is already in the system. If you’re not sure what’s in it, contact us before adding anything.
Before filling a new system, Hydratech advises that pipework should be clean and free of debris and biological contamination (BSRIA guide BG 29/2012), with air ingress kept to a minimum. A pressurised system is best.
Every Biotherm fluid is available in 5, 10 and 25 litre drums, 205 litre drums and 1000 litre IBCs, and Hydratech can supply it ready-mixed to the strength you need. Send us your system volume and we’ll come back with a price.
No products in the basket.